How to Solve the Low Pressure Failure During the Operation of the Chiller

Views: 166 Author: Site Editor Publish Time: Origin: Site

As industrial automation and precision manufacturing continue to advance, industrial chillers have become essential equipment in temperature control applications. When a chiller operates normally, it maintains stable suction and discharge pressures to ensure efficient cooling. However, when a low pressure failure occurs, it not only affects the cooling performance but can also increase energy consumption and lead to equipment downtime. Understanding the causes and solutions of chiller low pressure failure helps ensure smooth and reliable operation.

Effects of Low Pressure Failure in a Chiller

Before exploring the causes, it’s important to understand how low suction pressure impacts chiller performance. When the suction pressure of the compressor drops too low, several problems may appear.

First, energy consumption increases. Under low-pressure operation, the compressor motor runs at a reduced load, which can lead to longer operation times to reach the same cooling output. This inefficiency wastes electricity and increases operational costs.

Second, cooling capacity decreases. Low suction pressure means the refrigerant returning to the compressor is insufficient, reducing the system’s ability to absorb heat. As a result, the cooling effect weakens, and the equipment cannot achieve the desired temperature.

Water Cooled Scroll Chillers

Common Causes and Solutions for Low Pressure Failure

Now that we know the impact of low pressure failure, let’s explore the main causes and corresponding chiller troubleshooting methods.

1. Refrigerant Shortage or Leakage

A common cause of low suction pressure is insufficient refrigerant in the system. When refrigerant leaks through the compressor, condenser, or expansion valve connections, the system cannot maintain normal operating pressure. This triggers the low pressure alarm and causes the chiller to stop automatically.

Solution:
Inspect all connection points, joints, and valves for oil stains, which may indicate leaks. Once the leak is found and repaired, refill the refrigerant to the correct level according to manufacturer specifications. If you’re unsure about handling refrigerants safely, it’s best to contact a chiller manufacturer or professional technician.

2. Low Ambient Temperature

Environmental temperature also affects chiller performance. If the ambient or cooling water temperature is too low, the refrigerant pressure can drop. Low refrigerant oil temperature can also cause the refrigerant and oil to mix improperly, leading to a low pressure alarm.

Solution:
Close the cooling tower fan or throttle the cooling water flow to raise the cooling water temperature. Allow the industrial chiller to preheat for a longer time before operation so that the refrigerant oil reaches normal temperature. Maintaining a proper balance between cooling and heating is key to stable performance.

3. Blocked System Pipes or Filters

Blockages in the system are another frequent reason for low suction pressure. Over time, impurities or debris can accumulate in the filter drier, evaporator, or condenser, restricting refrigerant flow and reducing cooling efficiency.

Solution:
Clean or replace the filters, and flush the condenser and evaporator to ensure smooth refrigerant circulation. Regular preventive maintenance, such as checking for dirt buildup, can effectively reduce the occurrence of low pressure faults in chillers.

4. Expansion Valve Issues

The expansion valve controls the refrigerant flow into the evaporator. If the valve is too small, improperly adjusted, or damaged, it will reduce the refrigerant flow, lowering suction pressure and triggering a low pressure alarm.

Solution:
Check the expansion valve for blockage or malfunction. Adjust the opening as needed to ensure adequate refrigerant flow. If the valve is faulty, replace it with a model of the correct size and specification to restore normal cooling operation.

5. Relay or Electrical Faults

Sometimes, low pressure alarms are caused not by the refrigeration system but by electrical control errors. A malfunctioning low pressure relay can send a false signal that the pressure is too low, shutting down the system unnecessarily.

Solution:
Check the relay’s wiring and function using a multimeter. If the relay is damaged, replace it. To avoid unnecessary downtime, ensure all electrical components are dry, clean, and properly connected.

Water Cooled Scroll Chillers

Preventive Measures for Avoiding Low Pressure Failures

To minimize chiller low pressure failure, preventive maintenance is essential. Regular inspections can help identify small issues before they develop into costly breakdowns. Here are several preventive measures:

  • Monitor refrigerant levels regularly and top up as needed.

  • Clean filters and heat exchangers periodically to prevent blockages.

  • Ensure sufficient water flow through the evaporator and condenser.

  • Test the electrical system and sensors for accurate operation.

  • Keep operation logs to track temperature, pressure, and performance trends.

By implementing these steps, you can keep your industrial chiller system running smoothly and extend its service life.

Importance of Professional Maintenance and Support

When handling chiller faults, it’s crucial to follow proper safety and maintenance procedures. Low pressure failures can have multiple causes, and improper repair may worsen the issue. Partnering with a trusted chiller manufacturer ensures access to technical expertise, genuine replacement parts, and professional after-sales service.

Conclusion

In summary, low pressure failure in chillers can result from refrigerant leakage, low ambient temperature, system blockages, expansion valve faults, or electrical problems. By diagnosing these issues carefully and applying the appropriate solutions, you can restore stable performance and improve energy efficiency. Regular maintenance and timely intervention are the most effective ways to prevent downtime and reduce operational costs.

If your system experiences persistent chiller low pressure alarms, seek assistance from a professional chiller manufacturer like Kaydeli. With years of experience in industrial chiller design, production, and maintenance, Kaydeli provides reliable temperature control solutions tailored to different industries. Visit Kaydeli today to learn more about efficient and durable chillers that keep your operations running smoothly.

×